Industrial UPS | 20KVA/16KW | 3 Phases 4 Wires + PE | 380V/400V/415V | 384VDC
GRANKIA GLT3320 transformer based industrial online 3 phase ups 20kva can deliver robust and reliable power protection for critical applications. Engineered with advanced double-conversion technology and an integrated isolation transformer, it ensures maximum reliability, safety, and compatibility with industrial loads.
The industrial online 3 phase ups delivers 20 kVA of continuous output power. It provides high-availability power protection for manufacturing lines and automation controllers. It also protects process equipment, server rooms, and communications infrastructure. Clean, reliable three-phase power is essential in these areas.

Topology
Online double-conversion for continuous isolation between input power and load.
Transformer-based design
Input/output isolation transformers for superior electrical isolation, improved surge/lightning protection, and better tolerance of harsh industrial environments.
Input compatibility
Wide input voltage range and high overload capability to handle voltage sags, swells, and unbalanced three-phase input conditions common in factories.
Output quality
Tight voltage regulation (±1% typical), low total harmonic distortion (THD < 3% with linear loads), and configurable output voltage/frequency for regional compatibility.
Battery system
External battery cabinet support with scalable runtime; intelligent battery management and temperature-compensated charging extend battery life.
Redundancy and parallel capability
Support for N+1 parallel configurations (optional) to increase availability or capacity.
Protection features
Overload, short-circuit, over-temperature, input phase loss, input phase reversal detection, and surge protection.
Continuous clean power
Double-conversion isolates loads from grid anomalies—ideal for sensitive control electronics.
Improved safety and surge handling
Transformers add galvanic isolation and better transient/surge tolerance common in industrial environments.
Serviceability
Bypass configurations and modular components reduce mean time to repair and enable hot maintenance.
Integration-ready
Standard digital and dry-contact interfaces support remote monitoring, alerting, and facility control systems.
The GLT3320 UPS uninterrupted power supply is widely used in:
Industrial automation and process control systems
PLCs, HMIs, and motor drives requiring clean three-phase power
Data centers and server rooms with three-phase distribution
Telecom and network backbone equipment in industrial sites
Medical imaging and laboratory equipment requiring stable power
Renewable energy inverters and microgrid tie-ins needing ride-through capability
| Model | GLT3320 |
| Capacity | 20KVA/16KW |
| INPUT | |
| Nominal Voltage | 3 Phases 4 Wires + PE, 380Vac/400Vac/415Vac |
| Acceptable Voltage Range | ± 25% |
| Frequency | 50Hz/60Hz±5% (Automatically) |
| Power Factor | ≥0.95 |
| OUTPUT | |
| Rated Voltage | 3 Phases 4 Wires + PE, 380Vac/400Vac/415Vac ± 1% |
| Rated Frequency | 50Hz/60Hz±0.05%(By Battery) |
| Harmonic Distortion | Linear load<3%, Non-linear load<5% |
| Imbalance Voltage | Balance load≤1%, Imbalance load≤3% |
| Phase Shift Angle | Balance load≤1°, Imbalance load≤2° |
| Power Factor | 0.8 |
| Overload Capacity | 110%≥300Min, 125%≥10Min, 150%≥1Min |
| Crest Factor | 3:1 |
| Wave Form | Pure Sine Wave |
| Transfer Time | 0ms |
| AC Efficiency | > 93% |
| BATTERY | |
| Battery Type | Support VRLA Battery |
| Battery Voltage | 384Vdc |
| Max. Charging Current | 0.2AxC10 |
| Charging Time(Standard) | 12hours |
| SYSTEM | |
| Display | Touch LCD Display |
| IP Protection | IP20 |
| Parallel Mode | N+1 or N+X, max. parallel up to 8 units |
| ENVIRONMENT | |
| Humidity | 0~95% (non-condensing) |
| Altitude | <1000m (with increase of 100m,it will reduce output of 1%) max. 4000m |
| Noise | 53dB~60dB(Distance 1 Meter) |
| Operating Temperature | 0℃ to 40℃ |
| Storage Temperature | -15℃ to 50℃ |
| MANAGEMENT | |
| Communication Interface | RS232/RS485 |
| Remote Signaling | Dry contact (battery low,battery discharging,bypass/fault),EPO |
| Optional SNMP | Power management from SNMP manager and web browser |
| PHYSICAL | |
| Dimension, DxWxH(mm) | 485x695x1000 |
| Net Weight (Kg) | 184 |