Split Phase Solar Inverter | 3000W | 120V/240V 60Hz | 48VDC | Max. Charging: 60A
GRANKIA HS2030UH48L pure sine wave hybrid split phase inverter 3000w can work for modern off-grid, hybrid, and backup power systems. The 48v hybrid split phase inverter 3000w offers multiple essential functions in a compact, reliable unit. It includes a high-efficiency pure sine wave inverter and an advanced MPPT solar charge controller. There is also a smart AC battery charger and an automatic transfer switch (UPS function).
The 48V hybrid split phase inverter 3000w is specifically engineered for split-phase applications. It delivers 120V for standard household appliances. It also provides 240V for high-power loads like well pumps, dryers, air conditioners, or power tools. This makes it an ideal choice for North American homes, cabins, RVs, small businesses, and remote power setups.

True Pure Sine Wave Output
Provides stable, high-quality AC power identical to utility grid standards. This ensures safe and efficient operation of sensitive electronics, medical devices, and variable-speed motors. It also supports all household appliances without humming, overheating, or reduced lifespan.
Built-in MPPT Solar Charge Controller
High-efficiency tracking with wide PV input range up to 500V DC open circuit, maximizing solar harvest even in partial shade or variable weather.
AC Input & Charging
Supports grid/generator input with configurable priority modes (Solar/Battery first or Utility first) and powerful battery charging capability.
Support for Battery-Free Operation
In areas with reliable grid access, the inverter can combine solar PV input and grid power to supply loads directly — ideal for reducing electricity bills while maintaining backup capability.
Time-of-Use (TOU) Optimization
Advanced charging and discharging settings let users schedule operations based on peak/off-peak electricity rates. These settings significantly lower energy costs. Users can store solar energy during low-rate periods. They can discharge it during high-rate times.
Two-Level Anti-Backflow Protection
Ensures safe grid interaction by preventing excess solar power from flowing back into the grid without permission (CT sensor compatible for zero-export setups in regions requiring it).

| No. | Parts | Description |
| 1 | Solar Inverter | Split-phase solar inverter. |
| 2 | Battery Bank | Select the appropriate battery model according to the inverter–battery compatibility list. |
| 3 | PV String | A PV string consists of multiple photovoltaic modules connected in series. |
| 4 | Battery Breaker | Users should prepare a 2P DC circuit breaker. |
| 5 | AC Breaker | The AC breaker specifications for the LOAD and GRID must be the same for a given inverter model. The AC breaker should be provided by the end user. |
| 6 | SPDT Switch | To ensure the load can be powered by the grid during inverter maintenance, install an SPDT switch. |
| 7 | Generator | The generator’s maximum output power must be equal to or greater than the inverter’s rated power. |


| 1.LED Indicator | 2.LCD Display | 3.AC Input Breaker | 4.Label |
| 5.PV Input Switch | 6.Ground(PE) | 7.Power On/Off | 8.WiFi/GPRS (Option) |
| 9.AC Input Terminal | 10.Second Output / Generator Input Terminal | 11.Main Output Terminal | 12.COM Communication Port |
| 13.BMS Communication Port | 14.Dry Contact | 15.Battery Terminal | 16.PV Input Terminal (PV1/PV2) |

The solar panels generate enough energy to supply all household loads.
Priority of energy flow:
Home loads are powered first (appliances, lighting, etc.).
Batteries are charged with excess solar power.
Remaining energy is exported to the grid (feed-in).
This maximizes self-consumption and allows selling extra electricity to the utility grid.
Solar energy is available but not enough to cover all loads.
Priority of energy flow:
Solar power supplies loads first.
Batteries discharge to support the loads.
If still insufficient, power is imported from the grid.
This reduces grid dependency while keeping loads running continuously.
Solar panels stop producing energy.
Priority of energy flow:
Batteries discharge to power household loads.
If battery power is not enough, the grid supplies the loads.
This ensures uninterrupted power supply even at night.
| Model | HS2030UH48L |
| Rated Power | 3000W |
| Parallel Capability | No |
| AC / GENERATOR INPUT | |
| Nominal Voltage | 120Vac – 240Vac |
| Voltage Range | 90Vac-1400Vac(L-N), 180Vac-280Vac(L-L) |
| Frequency Range | 50Hz: 47-55Hz / 60Hz: 57-65Hz, ±0.3Hz |
| AC OUTPUT | |
| Nominal Voltage | 120Vac / 240Vac |
| Frequency | 50Hz / 60Hz ±0.3Hz(Auto) |
| Rated Current | 12.5A |
| Max. Efficiency | 92.00% |
| Transfer Time | 10ms |
| Waveform | Pure Sine Wave |
| BATTERY | |
| Battery Type | Lead-acid / Gel / LiFePO4 |
| Battery Rated Voltage | 48VDC |
| Battery Voltage Range | 40-60VDC |
| Default Charging Current | 60A |
| CHARGER | |
| Max. PV Array Power | 6000W |
| MPPT Range @ Operating Voltage | 90-450VDC |
| Max. PV Array Open Circuit Voltage | 500VDC |
| Max. Solar Charge Current | 60A |
| AC Charge Current | 40A |
| Maximum Charge Current | 60A |
| ENVIRONMENT | |
| Installation Method | Wall-mounted |
| Humidity | 5%~95%(No condensation) |
| Operation Temperature | -10℃ ~ 55℃ |
| Storage Temperature | -20℃ ~ 60℃ |
| Altitude | ≤2000m** |
| INTERFACE | |
| Communication | RS485/CAN, Optional Wi-Fi/GPRS |
| Display | LCD + LED |
| MECHANICAL | |
| Dimension, WxDxH (mm) | 350x133x540 |
| Weight (Kg) | 15.8 |
| CERTIFICATIONS | |
| Certificate | FCC, UL |
| Standard | FCC47 CFR Port 15, UL1741, TSCA, CA65 |