Industrial UPS | 200KVA/160KW | 3 Phases 4 Wires + PE | 380V/400V/415V | 480VDC
GRANKIA GLT33200 low frequency transformer based industrial ups 200kva provides reliable power protection. It ensures the continuity of operations in mission-critical environments.
The 3 phase 200kVA low-frequency transformer-based industrial UPS would deliver reliable and continuous power. It provides clean power to mission-critical equipment in chemical manufacturing plants. This is essential in other heavy-duty industrial environments. Built for high endurance and electrical robustness, it ensures stable operation. It remains stable even under harsh power conditions. It also withstands frequent voltage fluctuations or heavy inductive loads.

Low-Frequency Isolation Transformer
Equipped with a high-quality isolation transformer, the UPS provides complete galvanic isolation between input and output. This feature enhances system safety, reduces electrical noise, and supports reliable operation in environments with high electromagnetic interference (EMI).
Advanced DSP Control
Ensures precise voltage and frequency regulation, fast dynamic response, and intelligent fault detection for maximum operational stability.
Heavy-Duty 3 Phase Input and Output
This 3 phase 200kVA configuration is designed to handle industrial-grade loads. It supports motors, compressors, and critical process equipment without derating. This ensures full-load operation and system stability.
Industrial-Grade Design
Heavy-duty metal enclosure with superior heat dissipation, designed to withstand high ambient temperatures, dust, and continuous operation in demanding environments.
Wide Input Voltage Range
Ideal for unstable grids, the industrial UPS supports a wide input voltage and frequency range. This ensures reliable power supply even in regions with frequent fluctuations or voltage dips.
Comprehensive Monitoring and Communication
The unit includes an LCD/LED display. It has an RS232/RS485 interface and an optional SNMP module. These features allow remote monitoring and integration with energy management systems.

The GLT33200 200kVA Industrial UPS is ideal for:
Continuous online double-conversion protection eliminates downtime from utility disturbances.
Low-frequency transformer design provides superior fault tolerance, galvanic isolation, and long-term durability in harsh environments.
Wide input tolerance, generator compatibility, and modular paralleling allow tailored solutions for diverse applications.
High efficiency, intelligent battery management, and simplified maintenance reduce operating expenses and extend service life.
Engineered to meet strict safety standards for industrial installations and to protect personnel and equipment.
| Model | GLT33200 |
| Capacity | 200KVA/160KW |
| INPUT | |
| Nominal Voltage | 3 Phases 4 Wires + PE, 380Vac/400Vac/415Vac |
| Acceptable Voltage Range | ± 25% |
| Frequency | 50Hz/60Hz±5% (Automatically) |
| Power Factor | ≥0.95 |
| OUTPUT | |
| Rated Voltage | 3 Phases 4 Wires + PE, 380Vac/400Vac/415Vac ± 1% |
| Rated Frequency | 50Hz/60Hz±0.05%(By Battery) |
| Harmonic Distortion | Linear load<3%, Non-linear load<5% |
| Imbalance Voltage | Balance load≤1%, Imbalance load≤3% |
| Phase Shift Angle | Balance load≤1°, Imbalance load≤2° |
| Power Factor | 0.8 |
| Overload Capacity | 110%≥300Min, 125%≥10Min, 150%≥1Min |
| Crest Factor | 3:1 |
| Wave Form | Pure Sine Wave |
| Transfer Time | 0ms |
| AC Efficiency | > 93% |
| BATTERY | |
| Battery Type | Support VRLA Battery |
| Battery Voltage | 480Vdc |
| Max. Charging Current | 0.2AxC10 |
| Charging Time(Standard) | 12hours |
| SYSTEM | |
| Display | Touch LCD Display |
| IP Protection | IP20 |
| Parallel Mode | N+1 or N+X, max. parallel up to 8 units |
| ENVIRONMENT | |
| Humidity | 0~95% (non-condensing) |
| Altitude | <1000m (with increase of 100m,it will reduce output of 1%) max. 4000m |
| Noise | 53dB~62dB(Distance 1 Meter) |
| Operating Temperature | 0℃ to 40℃ |
| Storage Temperature | -15℃ to 50℃ |
| MANAGEMENT | |
| Communication Interface | RS232/RS485 |
| Remote Signaling | Dry contact (battery low,battery discharging,bypass/fault),EPO |
| Optional SNMP | Power management from SNMP manager and web browser |
| PHYSICAL | |
| Dimension, DxWxH(mm) | 1420x908x1650 |
| Net Weight (Kg) | 1176 |