FGG65-12 valve regulated lead acid gel battery 12v 65ah

Gel Battery 12V 65AH | Dimension: 350x167x178x178mm

SKU: FGG65-12 Category:

GRANKIA FGG65-12 valve regulated lead acid gel battery 12v 65ah consists of a gel, so no need maintenance to keep the battery working properly.

The deep cycle gel battery is using advanced valve-regulated technology with a narrow operating pressure range. It is equipped with explosion-proof and acid filters to avoid acid leakage and frequent maintenance.

GRANKIA battery grid technology is a lead antimony alloy grid mixture formulated specifically for use with T2 Technology. Thick grids reinforce the strength of the frame and reduce corrosion. The overall grid configuration is optimized to enhance current flow through the grid network providing exceptional battery performance, reducing downtime and lowering maintenance costs.

FGG65-12 valve regulated lead acid gel battery 12v 65ah

FGG65-12 valve regulated lead acid gel battery 12v 65ah

 

Gel Battery 12V 65AH Features

  • High quality fumed silica gel electrolyte:no flow, no leakage, all parts of the plate in uniform reaction.
  • Tight assembly technology: high efficiency discharge performance.
  • Gel electrolyte, battery with good heat dissipation ability, battery can work at lower and higher temperature.
  • High purity raw material: low self discharge rate.
  • Oxygen recombination technology: safe and eco-friendly.

Deep Cycle Battery Applications

  • Uninterrupted power supply(UPS)
  • Automotive and traction applications
  • Lighting equipment, fire alarms and security systems
  • Communication and telecom system
  • Solar energy system
  • High current drain applications
  • Fire alarms and security systems
  • Portable VTR/TV, tape recorders, radios, etc.
  • Various power toys and recreational equipment
  • Emergency power supplies in power generation plants and substations
  • Golf Cart

Solar Battery Details

sealed lead acid battery 12v copper terminalReliable and high performance lead acid battery

AGM lead acid battery in series or in parallel connection

Battery Storage Characteristics

Lead Acid Battery Discharge Characteristics Lead Acid Battery Charging Characteristics
Lead acid battery effect of temperature on capacity Lead acid battery self discharge characteristics
Lead acid battery relationship for open circuit voltage and residual capacity Lead acid battery the relationship for charging voltage and temperature
Lead acid battery floating life on temperature Lead acid battery cycle life on DOD

Valve Regulated Gel Battery FAQ

  1. What is a gel deep cycle battery?

    It is a valve regulated, maintenance free, lead acid battery. They are extremely robust and versatile. These type of batteries produce few fumes and can be used in places without much ventilation.

  2. How long does a deep cycle gel marine battery last?
  3. Can you overcharge a gel deep cycle battery?

 

The Articles You may Like

Nominal Voltage 12V(6 cells per unit)
Design Floating Life @25℃ 10 Years
Nominal Capacity @25℃(10 hour [email protected],10.80V) 65Ah
Capacity @25℃ 20 hour rate (3.61A,10.5V) 72.2Ah
 5 hour rate (11.9A,10.5V) 59.5Ah
1 hour rate (43.2A,9.6V) 43.2Ah
Internal Resistance Full Charged Battery@25℃ ≤7.0mΩ
Ambient Temperature Discharge -20℃~50℃
Charge -20℃~50℃
Storage -20℃~50℃
Max. Discharge Current@25℃ 650A(5s)
Capacity affected by Temperature

(10 hr Capacity )

40℃ 102%
25℃ 100%
0℃ 90%
-15℃ 70%
Self-Discharge@25℃ per Month 3%
Charge (Constant Voltage) @25℃ Standby Use Initial Charging Current Less than 16.3A

Voltage 13.6-13.8V

Cycle Use Initial Charging Current Less than 16.3A

Voltage 14.4-14.9V

 

Discharge Constant Current per Cell (Amperes at 25°C)

F.V/Time 15min 30min 45min 1h 2h 3h 5h 6h 8h 10h 20h
1.60V 109.7 68.3 49.0 43.2 26.4 19.3 12.4 10.5 7.6 6.76 3.75
1.65V 105.2 66.5 47.7 42.1 25.9 18.9 12.2 10.3 7.5 6.7 3.72
1.70V 100.6 64.6 46.4 40.9 25.4 18.6 12.1 10.1 7.4 6.63 3.68
1.75V 96.0 62.8 45.1 39.8 24.8 18.1 11.9 9.9 7.4 6.57 3.64
1.80V 91.5 61.0 43.7 38.6 24.2 17.7 11.9 9.8 7.3 6.5 3.61

Discharge Constant Powerper Cell (Watts at25°C)

F.V/Time 15min 30min 45min 1h 2h 3h 5h 6h 8h 10h 20h
1.60V 204.7 127.4 91.4 80.6 49.2 35.9 23.1 20.3 14.1 12.6 7.0
1.65V 196.1 123.9 88.9 78.5 48.3 35.3 22.8 20.0 14.0 12.5 6.9
1.70V 187.6 120.5 86.5 76.3 47.4 34.6 22.5 19.8 13.8 12.4 6.9
1.75V 179.1 117.1 84.0 74.2 46.2 33.8 22.1 19.4 13.7 12.2 6.8
1.80V 170.6 113.7 81.6 72.0 45.1 33.0 21.8 19.1 13.6 12.1 6.7